Siemens 6ES7313-5BE00-0AB0 Retrofit-Ready CPU for S7-300 Control Systems: Compatible Modernization and Smooth Legacy Upgrade
The Siemens 6ES7313-5BE00-0AB0 is a CPU 313C-2 DP compact controller within the SIMATIC S7-300 platform, purpose-built for industrial automation environments that demand reliable PROFIBUS DP communication, integrated I/O, and long-term backward compatibility. As legacy S7-300 installations age and original CPU modules reach end-of-life, the 6ES7313-5BE00-0AB0 has become a primary retrofit and replacement solution for system integrators, maintenance engineers, and OEM panel builders managing existing control architectures.
This CPU integrates 24 digital inputs, 16 digital outputs, 4 analog inputs, and 2 analog outputs directly on-board, reducing the need for additional SM 321 or SM 322 signal modules in compact cabinet configurations. Its onboard PROFIBUS DP master/slave interface supports network speeds up to 12 Mbit/s, making it fully compatible with existing DP field devices including ET 200S distributed I/O stations, SINAMICS drives, and third-party PROFIBUS peripherals already installed in the field.
Upgrade Compatibility Table
| Parameter | Details |
|---|---|
| SKU / Order Number | 6ES7313-5BE00-0AB0 |
| Product Series | SIMATIC S7-300 |
| CPU Type | CPU 313C-2 DP (Compact CPU with DP Interface) |
| Onboard Digital I/O | 24 DI / 16 DO |
| Onboard Analog I/O | 4 AI / 2 AO |
| Communication Interface | MPI + PROFIBUS DP (Master/Slave), up to 12 Mbit/s |
| Backplane / Rack Compatibility | S7-300 standard rail (UR1, UR2); slots 2–11 |
| Power Supply Compatibility | PS 307 (2A / 5A / 10A); 24 VDC load voltage |
| Common Replaced Models | 6ES7313-5BE01-0AB0, 6ES7313-5BF03-0AB0, 6ES7312-1AE13-0AB0 |
| Programming Software | STEP 7 V5.x / TIA Portal V13 SP1 and above |
| Installation Requirement | Slot 2 on S7-300 rack; no additional bus connector required for CPU slot |
| Commissioning Tool | PC Adapter USB A2 (6ES7972-0CB20-0XA0) or MPI/PROFIBUS cable |
| Warranty | 12 Months — covers hardware defects under normal operating conditions |
Retrofit Planning for Existing Automation Systems
When planning a retrofit around the 6ES7313-5BE00-0AB0, engineers must conduct a thorough pre-replacement audit of the existing control cabinet. Begin by documenting the current rack layout: confirm the positions of all installed modules including SM 321 digital input modules, SM 322 digital output modules, SM 331 analog input modules, and any CP 342-5 or CP 343-1 communication processors occupying expansion slots. The 6ES7313-5BE00-0AB0 installs exclusively in slot 2 of the S7-300 rack, and its onboard I/O is addressed starting at the default byte addresses configured in STEP 7 hardware configuration — these must be verified against the existing program’s I/O mapping before the swap.
Power supply sizing is a critical pre-check. The PS 307 5A power supply is typically sufficient for a compact S7-300 system with this CPU and up to four signal modules, but if the cabinet also powers 24 VDC field devices through the same rail, a PS 307 10A unit may be required. Verify the total current draw across all installed modules and connected field devices before committing to the replacement.
Terminal wiring on the onboard I/O connector of the 6ES7313-5BE00-0AB0 uses a 40-pin front connector. If the previous CPU was a non-compact variant such as the CPU 313 (6ES7313-1AD03-0AB0), the onboard I/O did not exist, and field wiring for those signals was routed to separate SM modules. In this case, the retrofit plan must account for re-routing or re-terminating those field cables to the compact CPU’s front connector — a task that requires careful labeling and loop testing before power-up.
For systems using IM 360 / IM 361 expansion rack interfaces to connect additional racks, confirm that the module address assignments in the STEP 7 hardware configuration remain consistent after the CPU swap. The PROFIBUS DP network configuration — including all slave addresses for connected ET 200S stations, SINAMICS G120 drives, and third-party DP devices — must be re-downloaded to the new CPU after the hardware configuration is compiled and transferred. Any HMI panels connected via MPI, such as TP 177B or MP 277 operator panels, will require a re-established communication link and may need their project re-downloaded if the MPI address of the CPU changes.
Before final commissioning, perform a full I/O force test using STEP 7’s variable table to verify each digital and analog channel responds correctly. Check the PROFIBUS DP diagnostic buffer for any slave communication faults and resolve them before returning the system to automatic mode. All units supplied by SMARTNEXMSK are pre-tested for power-on functionality and shipped with a 12-month warranty covering hardware defects under normal operating conditions.
Downtime Control During System Migration
Minimizing production downtime during a CPU replacement requires a structured migration sequence. The most effective approach is to prepare the replacement 6ES7313-5BE00-0AB0 offline before the maintenance window begins. Using STEP 7 or TIA Portal, load the existing program backup — including the complete hardware configuration, symbol table, and all OB/FB/FC/DB blocks — onto the new CPU via a PC Adapter USB A2 (6ES7972-0CB20-0XA0) or a compatible MPI programming cable. Verify the program compiles without errors and that the hardware configuration matches the physical rack layout exactly.
During the maintenance window, power down the control cabinet using the PS 307 power supply switch. Remove the existing CPU by releasing the bus connector and front panel screws, then seat the 6ES7313-5BE00-0AB0 in slot 2. Reconnect the front connector wiring to the onboard I/O terminals, ensuring all 24 VDC input commons and output load circuits are correctly terminated. Restore power and confirm the CPU reaches RUN mode without fault LEDs. If the SF (System Fault) LED illuminates, connect the programming device and review the diagnostic buffer — common causes include PROFIBUS DP slave address mismatches or missing hardware configuration downloads.
For systems where even brief interruptions are critical, consider using a hot-standby strategy with a second S7-300 rack running in parallel during the transition period, or coordinate the swap during a scheduled production break. Retaining a full STEP 7 project archive on a dedicated engineering PC ensures that program logic can be restored within minutes if an unexpected issue arises during commissioning. SMARTNEXMSK recommends completing all wiring checks, program downloads, and I/O force tests before declaring the system ready for production restart.
Retrofit Support FAQ
Q1: Is the 6ES7313-5BE00-0AB0 a direct drop-in replacement for the 6ES7313-5BE01-0AB0 or 6ES7313-5BF03-0AB0?
In most cases, yes. These models share the same CPU 313C-2 DP hardware platform and are functionally compatible. However, firmware revision differences may affect specific function block behavior. Always re-download the hardware configuration and program after the swap and verify operation in STEP 7 diagnostic mode before returning to production.
Q2: What wiring changes are needed when replacing a non-compact CPU 313 with this compact CPU?
The 6ES7313-5BE00-0AB0 includes onboard I/O via a 40-pin front connector that non-compact CPUs do not have. If your existing system used separate SM 321/SM 322 modules for those I/O points, you may choose to retain those modules and simply ignore the onboard I/O, or re-route field wiring to the onboard connector to free up rack slots. Document all terminal assignments before making any wiring changes.
Q3: How do I verify PROFIBUS DP compatibility with my existing field devices after the CPU swap?
After downloading the hardware configuration to the new CPU, switch to RUN mode and open the STEP 7 hardware diagnostics. Check the DP master system for any slave communication errors. Each slave — whether an ET 200S station, a SINAMICS drive, or a third-party DP device — should show a green status. If faults appear, verify that slave addresses match the configuration and that the PROFIBUS cable termination resistors are correctly set at both ends of the network segment.
Q4: What does the 12-month warranty cover, and how is it handled?
All 6ES7313-5BE00-0AB0 units supplied by SMARTNEXMSK carry a 12-month warranty covering hardware defects arising under normal operating conditions. Each unit undergoes power-on testing and functional verification before shipment. In the event of a warranty claim, contact our sales team with the order reference and a description of the fault. We will arrange replacement or repair with priority handling to minimize your system downtime.