Description

ABB CM-MPS.21S 1SVR730885R3300 Retrofit-Ready Voltage Relay Overview

ABB CM-MPS.21S 1SVR730885R3300 Retrofit-Ready Voltage Relay for CM-MPS Control Systems

The ABB CM-MPS.21S (part number 1SVR730885R3300) is a three-phase voltage monitoring relay engineered for seamless retrofit integration into existing CM-MPS series control architectures. Whether you are replacing an end-of-life unit in a legacy distribution panel, upgrading a dated protection circuit, or restoring a critical interlock loop after an unplanned failure, the CM-MPS.21S delivers the electrical compatibility and dimensional precision required for a low-disruption, drop-in substitution. Its DIN-rail mounting footprint, standard 22.5 mm width, and screw-terminal wiring layout match the original CM-MPS installation envelope, allowing maintenance engineers to complete a swap without panel re-drilling, cable re-routing, or PLC program modification.

Sourced directly from verified supply channels and pre-tested prior to shipment, every CM-MPS.21S unit leaves our warehouse with full functional verification covering under-voltage, over-voltage, phase-loss, and phase-sequence detection thresholds. Stock is maintained on a continuous basis to support both emergency replacement orders and planned maintenance schedules, with a 12-month warranty covering all units against manufacturing defects and functional failure under normal operating conditions.

Upgrade Compatibility Table

Parameter Specification / Retrofit Note
Part Number CM-MPS.21S / 1SVR730885R3300
Brand / Series ABB / CM-MPS Series
Function Three-Phase Voltage Monitoring Relay (Under/Over-Voltage, Phase Loss, Phase Sequence)
Supply Voltage 3 × 160–300 V AC (L-N), 50/60 Hz
Output Relay 1 × SPDT, 6 A / 250 V AC
Mounting DIN Rail (35 mm), 22.5 mm width — direct fit for CM-MPS panel cutouts
Terminal Compatibility Screw terminals, identical pin assignment to CM-MPS.21 and CM-MPS.22 variants
Communication Standalone relay output; compatible with hardwired interlock and safety relay circuits
Replacement Compatibility Direct retrofit for CM-MPS.21, CM-MPS.21S, CM-MPS.22S legacy units
Commissioning Note Verify threshold potentiometer settings (U<, U>, t) after installation; no firmware required
Operating Temperature −20 °C to +60 °C
Protection Rating IP40 (front face), IP20 (terminals)
Certifications CE, UL, cUL, GL
Origin Germany
Warranty 12 Months — covers functional failure and manufacturing defects

Retrofit Planning for Existing Automation Systems

A successful CM-MPS.21S retrofit begins well before the unit arrives on site. The first step is a thorough review of the existing panel documentation: confirm the supply voltage range, the output relay wiring to downstream contactors or safety relays, and the current threshold settings recorded during the original commissioning. In many legacy installations, the CM-MPS.21 or CM-MPS.22S was wired in series with an ABB ESB contactor or a PSR soft-starter enable circuit, meaning the output relay state directly governs motor start permission. Any interruption to this interlock chain during the swap must be managed with a temporary bypass or a coordinated shutdown window.

For panels built around the ABB S200 series miniature circuit breakers and equipped with an ABB F200 residual current device, the incoming supply to the CM-MPS.21S should be verified against the breaker rating before energizing the replacement unit. Where the original installation included an ABB CP-S 24 VDC power supply module feeding auxiliary circuits, confirm that the 24 V rail remains stable during the relay changeover, as voltage dips can trigger nuisance trips in adjacent ABB CR-M relay modules or CM-EFS frequency monitoring relays sharing the same bus.

Terminal wiring on the CM-MPS.21S follows the standard ABB CM-series pinout: terminals A1/A2 for supply, 11/12/14 for the output relay, and L1/L2/L3 for the monitored three-phase input. If the legacy unit was a CM-MPS.21 (without the S suffix), the terminal assignment is identical, making the substitution straightforward. However, if the original installation used an ABB CM-MPS.22S with dual-relay output, note that the CM-MPS.21S provides a single output relay; the second relay function must be replicated by an additional ABB CM-ENN voltage monitoring relay or handled in the PLC logic if a Modbus-capable controller such as an ABB AC500 CPU module is present in the cabinet.

Where the control system includes an ABB Panel Builder or an older ABB Advant OCS rack, the CM-MPS.21S output is typically wired to a digital input card. Confirm the DI card input voltage range (typically 24 V DC) and ensure the relay dry contact is correctly configured as normally open or normally closed to match the original interlock logic. No changes to the PLC program are required if the wiring polarity and contact configuration are preserved. For systems using an ABB CP600 HMI panel, the voltage monitoring status displayed on the HMI screen is driven by the DI tag mapped to the relay output — this mapping remains valid after the swap without any HMI screen modification.

Downtime Control During System Migration

Minimizing production downtime during a CM-MPS.21S replacement requires a structured approach. Begin by scheduling the swap during a planned maintenance window or a low-production shift. Before de-energizing the panel, photograph the existing wiring, record the potentiometer positions for the under-voltage (U<), over-voltage (U>), and time-delay (t) thresholds, and note the LED status of the original unit to confirm it was operating within normal parameters prior to removal.

With the panel isolated and locked out per LOTO procedures, remove the faulty CM-MPS.21S or legacy CM-MPS.21 unit from the DIN rail. Transfer the terminal wiring to the replacement unit terminal by terminal, using the original wiring photograph as reference. Re-energize the supply and verify the green LED illuminates, confirming the three-phase voltage is within the set thresholds. Test the output relay by temporarily reducing the monitored voltage below the U< threshold using a variable transformer if available, or by confirming the relay drops out during a controlled phase-loss simulation. Once the relay response is confirmed, restore the interlock circuit and release the system to normal operation.

For critical continuous-process applications — such as water treatment pump stations, compressor control panels, or conveyor drive cabinets — where even a brief interruption is unacceptable, a hot-standby approach using a pre-wired spare CM-MPS.21S on a plug-in terminal block adapter can reduce the physical swap time to under two minutes. This approach is particularly effective in panels where the CM-MPS.21S is mounted alongside an ABB UMC100 motor management relay or an ABB PSTB soft-starter, where coordinated restart sequencing must be preserved.

Retrofit Support FAQ

Q1: Is the CM-MPS.21S a direct drop-in replacement for the CM-MPS.21 and CM-MPS.22S?
The CM-MPS.21S is a direct replacement for the CM-MPS.21 in terms of terminal assignment, DIN-rail footprint, and single-relay output. For CM-MPS.22S applications requiring dual relay output, an additional monitoring relay must be added to replicate the second output channel. Confirm the threshold settings from the original unit before commissioning the replacement.

Q2: What pre-shipment testing is performed on each unit?
Every CM-MPS.21S unit undergoes functional verification prior to dispatch, including under-voltage trip, over-voltage trip, phase-loss detection, and output relay continuity testing. Units that do not meet ABB specification thresholds are quarantined and not shipped. A 12-month warranty is provided from the date of shipment.

Q3: Can the CM-MPS.21S be used with existing PLC programs without modification?
Yes, provided the output relay wiring polarity and contact configuration (NO/NC) are preserved during the swap. The CM-MPS.21S presents the same electrical interface to the PLC digital input as the original unit. No firmware, parameter file, or program changes are required in the connected controller.

Q4: What is the long-term supply availability for the CM-MPS.21S?
We maintain continuous stock of the CM-MPS.21S to support both emergency replacement and planned maintenance programs. Orders are processed and dispatched within 1–3 business days. For large-quantity or scheduled procurement requirements, contact our sales team to arrange a supply agreement with guaranteed lead times.


© 2026 SMARTNEXMSK. All rights reserved.
Original Source: https://smartnexmsk.com
Contact: [email protected] | +86 18259474341

Catalog Paths

Continue from this exact model

Use the live catalog paths below to compare the same brand, product type, or series before sending your RFQ.

RFQ Intent Desk

Choose the right sourcing path for this model

Each action carries the product model and intent into the inquiry record so the sales follow-up starts with useful context.

Exact Model Quote

Use this path when the SKU, brand, quantity, and destination are already confirmed.

Start
Replacement Check

Use this path for old, obsolete, or uncertain models that need compatibility review.

Start
Quality Confirmation

Ask for label photos, packing notes, documentation, or pre-shipment checks.

Start
Urgent Dispatch

Route downtime or maintenance requests with target dispatch timing and courier country.

Start
Request Quote WhatsApp Email