E+H FMU41-ARB2A2 Retrofit-Ready Radar Level Transmitter for Micropilot Control Systems
The Endress+Hauser FMU41-ARB2A2 is a non-contact radar level transmitter from the Micropilot M series, engineered for reliable continuous level measurement in liquids, pastes, and bulk solids. For facilities operating legacy Micropilot FMU40, FMU42, or FMU43 units — or those migrating from older ultrasonic transmitters such as the Prosonic M FMU40 — the FMU41-ARB2A2 represents a proven, cost-effective retrofit path that preserves existing wiring infrastructure and minimizes engineering rework.
This unit operates on a 2-wire loop-powered 4–20 mA / HART signal, making it directly compatible with most existing DCS and PLC input cards without signal conditioning changes. Whether your control platform is a Siemens S7-300, an ABB AC500, or a Yokogawa CENTUM VP, the FMU41-ARB2A2 integrates cleanly into the existing I/O architecture. The transmitter supports HART 5/6 communication, enabling remote configuration via FieldCare, DeviceCare, or any HART-compatible handheld communicator without interrupting the process loop.
Upgrade Compatibility Table
| Parameter | FMU41-ARB2A2 (This Unit) | Typical Legacy Unit (FMU40 / Ultrasonic) | Retrofit Notes |
|---|---|---|---|
| Measurement Technology | Free-space radar (26 GHz) | Ultrasonic / older radar | No process contact; suitable for vapour/foam environments |
| Signal Output | 4–20 mA / HART 5/6 | 4–20 mA / HART 5 | Direct drop-in; no signal converter required |
| Power Supply | 10.5–45 V DC (2-wire) | 10.5–36 V DC (2-wire) | Verify loop supply voltage at terminal head before installation |
| Process Connection | G 1½ / MNPT 1½ / flange options | G 1½ / MNPT 1½ | Confirm nozzle size and flange rating; adapter flanges available |
| Communication Protocol | HART 5/6 | HART 5 | Fully backward-compatible; existing HART multiplexers unaffected |
| Housing / Enclosure | Aluminium, IP67 / IP68 | Aluminium, IP67 | Same conduit entry; existing cable glands reusable |
| Commissioning Tool | FieldCare / DeviceCare / HART handheld | FieldCare / Commuwin II | Update DTM library before commissioning; Commuwin II not required |
| Warranty | 12-Month Warranty — Covered from date of shipment | ||
Retrofit Planning for Existing Automation Systems
A successful FMU41-ARB2A2 retrofit begins well before the unit arrives on site. Engineers should pull the existing loop drawing and verify the terminal block wiring at the field junction box. The FMU41-ARB2A2 uses a standard two-wire connection at terminals L+ and L−, identical to most Micropilot M predecessors, so existing shielded twisted-pair cable is typically reusable without re-pulling.
On the control system side, confirm that the AI card — whether a Siemens SM331, a Rockwell 1756-IF16, or an equivalent analogue input module — is configured for 4–20 mA HART. If the existing card is a legacy voltage-input type, a signal converter or card swap may be required before the FMU41-ARB2A2 can be commissioned. For systems using a PROFIBUS PA segment with a DP/PA coupler such as the Pepperl+Fuchs KFD2-BR-1.PA, note that the FMU41-ARB2A2 ARB2A2 order code specifies HART output, not PROFIBUS PA — confirm the order code suffix matches your bus architecture before procurement.
Where the existing installation uses a Rosemount 3300 or a Vega VEGAPULS series transmitter as the incumbent device, the FMU41-ARB2A2 can serve as a cross-brand replacement provided the process nozzle geometry is compatible. A nozzle adapter or standpipe extension may be needed to achieve the correct minimum distance and beam angle clearance. Document the existing tank geometry — diameter, nozzle height, internal obstructions — and run the Endress+Hauser Applicator sizing tool to confirm antenna selection before ordering.
For facilities running a Yokogawa STARDOM or Honeywell Experion PKS DCS, the FMU41-ARB2A2 integrates via the standard HART I/O channel. Load the updated EDDL or FDT/DTM device description into the asset management layer before the cutover window. If the plant uses a Fieldbus Foundation H1 segment, a separate FOUNDATION Fieldbus variant of the Micropilot M must be specified — the ARB2A2 suffix is HART-only.
Spare parts planning should include a replacement Combifit M process adapter, a set of terminal head O-rings, and a spare FMU41 antenna insert if the existing antenna shows corrosion or mechanical wear. Stocking a Micropilot FMU42 or FMU44 as a higher-specification backup is advisable for critical level loops where measurement failure triggers a process shutdown.
Downtime Control During System Migration
Minimising unplanned downtime during a radar transmitter swap requires a structured cutover plan. Begin by placing the affected control loop in manual mode at the DCS or PLC operator station, locking the output at the last known good value. This preserves process continuity while the field device is physically exchanged.
Before breaking the process connection, confirm that the vessel can be isolated or that the measurement point is in a safe state for maintenance access. Once the FMU41-ARB2A2 is mechanically installed and the terminal wiring is reconnected, power the loop and verify the 4–20 mA signal at the marshalling cabinet before releasing the loop back to automatic control. Use a HART communicator or a laptop running DeviceCare to perform a quick-start configuration — entering the empty distance (E), full distance (F), and output damping value — before the loop goes live.
For plants with a Siemens PCS 7 or ABB 800xA control system, the device tag and HART address must match the existing configuration in the asset management database. A mismatch will trigger a device alarm in the AMS or FDM layer without affecting the 4–20 mA signal, but it should be resolved during the commissioning window to maintain a clean asset register. If the original program logic includes a level switch interlock derived from the transmitter signal, verify the switch-point setpoints in the PLC ladder or function block diagram before returning the loop to service.
All units supplied by SMARTNEXMSK undergo pre-shipment functional testing — loop current output verification, HART communication check, and housing integrity inspection — so the device arrives ready for installation without requiring a bench calibration step. This reduces the on-site commissioning window and supports a same-shift cutover in most standard applications.
Retrofit Support FAQ
Q1: Is the FMU41-ARB2A2 a direct replacement for the FMU40-ARB2A2?
Yes. The FMU41 series is the direct successor to the FMU40 within the Micropilot M family. The terminal assignment, housing footprint, and 4–20 mA / HART signal interface are identical. No wiring changes are required in the majority of installations. Confirm the process connection thread type (G or NPT) matches the existing nozzle before ordering.
Q2: Can I commission the FMU41-ARB2A2 without a laptop or FieldCare?
Yes. The FMU41-ARB2A2 features an onboard 4-button keypad and local display (if the display option is included in the order code). Basic commissioning — empty calibration, full calibration, and output damping — can be performed entirely from the local display without a PC or HART handheld. For advanced diagnostics or remote asset management integration, FieldCare or DeviceCare is recommended.
Q3: What wiring checks should I perform before powering the replacement unit?
Verify loop supply voltage at the terminal head (minimum 10.5 V DC under load), confirm cable shield is grounded at one end only, and check that the existing cable insulation resistance is within specification. Inspect the terminal block for corrosion or loose connections. Ensure the loop resistance (cable + input card) does not exceed the HART communication window (typically 230–1100 Ω for HART). Document terminal assignments before disconnecting the old device.
Q4: What does the 12-month warranty cover?
All FMU41-ARB2A2 units supplied by SMARTNEXMSK carry a 12-month warranty from the date of shipment, covering manufacturing defects, component failure under normal operating conditions, and HART communication faults attributable to the device. The warranty does not cover damage resulting from incorrect installation, overvoltage, or process conditions outside the rated specification. Warranty claims are supported by our technical team at [email protected].