The Allen-Bradley 1336-PB-SP23C is a retrofit-ready power board designed as a direct replacement for aging or failed power supply assemblies within the 1336 PLUS series AC variable frequency drive platform. As legacy 1336 PLUS drives approach end-of-service life and OEM spare parts become increasingly scarce, the 1336-PB-SP23C provides a verified, drop-in upgrade path that preserves existing control wiring, terminal layouts, and drive enclosure dimensions — minimizing engineering rework and unplanned downtime on the production floor.
Industrial facilities running 1336 PLUS drives in pump control, conveyor systems, HVAC air handling, compressor regulation, and material handling lines rely on the power board as the core energy conversion and gate-drive interface component. When this board fails, the entire drive becomes inoperable. Sourcing a verified 1336-PB-SP23C replacement from a stocked supplier with pre-shipment testing and a 12-month warranty is the fastest path to restoring production continuity without committing to a full drive replacement or a costly platform migration.
SMARTNEXMSK maintains ready inventory of the 1336-PB-SP23C and related 1336 PLUS spare components, with each unit subject to functional verification prior to dispatch. Global shipping is available with lead times suitable for both planned maintenance windows and emergency breakdown recovery scenarios.
Upgrade Compatibility Table
| Parameter | Detail |
|---|---|
| Replacement SKU | 1336-PB-SP23C |
| Compatible Drive Series | Allen-Bradley 1336 PLUS (1336S, 1336 PLUS II) |
| Board Function | Power Supply / Gate Drive Interface Board |
| Mounting Interface | Direct backplane mount — no bracket modification required |
| Terminal Compatibility | Matches OEM terminal block layout; no rewiring required |
| Communication Compatibility | Compatible with existing 1336-GM-x and 1336-MOD-x communication adapter modules |
| Firmware Dependency | No firmware reflash required for direct board swap |
| Installation Requirement | Verify DC bus discharge before removal; torque terminals to OEM spec |
| Commissioning Note | Re-run drive autotune after board replacement if motor parameters were stored on board |
| Warranty | 12 Months — covers manufacturing defects and functional failure under normal operating conditions |
Retrofit Planning for Existing Automation Systems
A successful 1336-PB-SP23C retrofit begins well before the replacement board arrives on site. Engineers should start by auditing the full drive assembly to identify all components that interact with the power board. In a typical 1336 PLUS installation, the power board interfaces directly with the 1336-BRF-SP1 brake resistor assembly, the 1336-MOD-D4 DeviceNet communication module, and the 1336-GM-1 gate module — all of which should be inspected for wear or corrosion during the same maintenance window.
The control wiring connected to the 1336-PB-SP23C typically includes 24 VDC logic power, analog reference signals from the operator interface, and digital I/O from the PLC — often a 1756-IB16 digital input module or a 1756-OB16E digital output module in a ControlLogix rack. Before disconnecting any wiring, photograph all terminal connections and export the drive parameter file using DriveExplorer or DriveExecutive software. This parameter backup is critical: it preserves acceleration/deceleration ramps, current limits, fault thresholds, and PID tuning values that would otherwise need to be re-entered manually after the swap.
For facilities that have already migrated their control platform to a 1769-L30ER CompactLogix or 1756-L73 ControlLogix processor, the 1336 PLUS drive can continue to operate as a legacy peripheral via hardwired I/O or a retained 1336-MOD-D4 DeviceNet link, avoiding the need for a full drive replacement during the power board service. If the site is planning a longer-term migration to a PowerFlex 525 or PowerFlex 755 drive platform, replacing the 1336-PB-SP23C now extends the operational life of the existing drive by 3–5 years, providing a controlled transition timeline rather than a forced emergency replacement.
I/O wiring should be verified against the original panel drawings before power-up. Pay particular attention to the analog input scaling on terminals TB1 and TB2, which control speed reference. If the site uses a 1336-QOUT-SP1 output filter or a line reactor on the input side, these components remain in place and do not require reconfiguration after the board swap. The 1336-PB-SP23C is also compatible with existing HMI screens built on PanelView 550 or PanelView Plus 600 terminals communicating via DH-485 or DeviceNet — no HMI screen modifications are required for a like-for-like board replacement.
Downtime Control During System Migration
Minimizing production downtime during a 1336-PB-SP23C swap requires a structured pre-work checklist executed before the maintenance window opens. The following sequence is recommended for sites where the drive controls a critical process:
1. Pre-shutdown preparation: Export all drive parameters to a laptop running DriveExplorer. Confirm the backup file opens correctly and all parameter groups are readable. Label all control wiring at the terminal block before disconnection. Photograph the wiring from multiple angles.
2. Safe isolation: Open the main disconnect and verify DC bus voltage has discharged below 50 VDC using a calibrated meter before touching any internal components. The 1336 PLUS bus capacitors can retain dangerous charge for several minutes after power removal.
3. Board removal and installation: Remove the 1336-PB-SP23C by releasing the backplane connector and unscrewing the four mounting points. Install the replacement board in reverse order. Torque all terminal screws to the values specified in publication 1336 PLUS-5.2. Reconnect control wiring in the documented sequence.
4. Parameter restore and autotune: Restore the parameter backup via DriveExplorer. If motor nameplate data was stored on the original board and is not recoverable from the backup, re-enter motor voltage, current, frequency, speed, and power ratings manually. Run a static autotune before enabling the drive under load.
5. Functional verification: Jog the motor at low speed (5–10 Hz) and verify direction, speed reference tracking, and fault-free operation before returning the drive to automatic control from the PLC. Confirm that the DeviceNet or DH-485 communication link re-establishes correctly and that the PLC program resumes normal sequencing without fault.
With proper preparation, a 1336-PB-SP23C board swap can typically be completed within a 2–4 hour planned maintenance window, preserving the existing control program logic, HMI screens, and field wiring without modification.
Retrofit Support FAQ
Q: Is the 1336-PB-SP23C a direct drop-in replacement for the original Allen-Bradley power board in my 1336 PLUS drive?
A: Yes. The 1336-PB-SP23C is designed as a form-fit-function replacement for the OEM power board in the 1336 PLUS drive series. The backplane connector, mounting hole pattern, and terminal block layout are identical to the original, requiring no mechanical modification to the drive enclosure or control wiring.
Q: What commissioning steps are required after installing the 1336-PB-SP23C?
A: After installation, restore your saved parameter file using DriveExplorer or DriveExecutive. If motor parameters are not recoverable, re-enter motor nameplate data and run a static autotune. Verify communication link re-establishment (DeviceNet or DH-485) and perform a low-speed jog test before returning the drive to automatic operation.
Q: Can I use the 1336-PB-SP23C in a 1336 PLUS II drive, or only the original 1336 PLUS?
A: The 1336-PB-SP23C is compatible with both the 1336 PLUS and 1336 PLUS II drive variants within the applicable horsepower and voltage rating range. Please confirm your drive catalog number and firmware revision against the compatibility table or contact our technical team before ordering if you have a non-standard configuration.
Q: What does the 12-month warranty cover, and what is the claims process?
A: The 12-month warranty covers manufacturing defects and functional failure under normal operating conditions from the date of shipment. It does not cover damage resulting from incorrect installation, overvoltage events, or environmental contamination. To initiate a warranty claim, contact [email protected] with your order number, a description of the fault, and any available fault code data from the drive display.