Allen-Bradley 1746-P4 Retrofit-Ready Power Supply for SLC 500 Control Systems
The Allen-Bradley 1746-P4 is a modular power supply designed for the SLC 500 series programmable logic controller platform. As legacy SLC 500 installations continue to operate across manufacturing, utilities, and process industries, the 1746-P4 has become one of the most sought-after retrofit components for engineers managing aging control infrastructure. Whether you are replacing a failed unit, upgrading power capacity in an expanded rack, or migrating from an older 1746-P2 or 1746-P3 supply, the 1746-P4 delivers the output headroom and form-factor compatibility required for a smooth, low-risk transition.
Rated at 10A at 5VDC and 1.5A at 24VDC, the 1746-P4 supports the full range of SLC 500 I/O modules installed in 1746-A4, 1746-A7, 1746-A10, and 1746-A13 chassis configurations. Its backplane interface is fully compatible with the SLC 5/03, SLC 5/04, and SLC 5/05 processor families, making it the preferred choice when upgrading from lower-capacity supplies without altering the existing rack layout or rewiring the control cabinet.
Upgrade Compatibility Table
| Parameter | Detail |
|---|---|
| SKU / Part Number | 1746-P4 |
| Brand / Manufacturer | Allen-Bradley (Rockwell Automation) |
| Compatible Series | SLC 500 (SLC 5/01, 5/02, 5/03, 5/04, 5/05) |
| Compatible Chassis | 1746-A4, 1746-A7, 1746-A10, 1746-A13 |
| Output Rating | 10A @ 5VDC; 1.5A @ 24VDC |
| Input Voltage | 85–265VAC, 47–63Hz (universal input) |
| Replaces / Upgrades From | 1746-P1, 1746-P2, 1746-P3 |
| Backplane Interface | Direct-mount, SLC 500 standard backplane connector |
| Installation Type | Drop-in, no chassis modification required |
| Communication Compatibility | DH+, DH-485, Ethernet/IP (via SLC 5/05 processor) |
| Commissioning Notes | Verify total backplane load before installation; re-seat all I/O modules after swap |
| Warranty | 12 Months from date of shipment |
Retrofit Planning for Existing Automation Systems
Successful integration of the 1746-P4 into an existing SLC 500 system begins with a thorough audit of the current control cabinet. Engineers should document the total backplane current draw across all installed modules — including analog input cards such as the 1746-NI4, digital output modules like the 1746-OB16, and any specialty modules such as the 1746-BAS BASIC module or 1746-HSCE high-speed counter — to confirm the 1746-P4’s 10A capacity is sufficient before proceeding.
Terminal wiring on the 1746-P4 follows the standard SLC 500 power supply pinout. If the existing installation uses a 1746-P2 or 1746-P3, the AC input terminals, chassis ground lug, and 24VDC auxiliary output connections are physically compatible, reducing rewiring time significantly. Confirm that the incoming AC supply is within the 85–265VAC universal input range and that the branch circuit protection is rated appropriately for the new supply’s inrush characteristics.
For systems running SLC 5/04 or SLC 5/05 processors with active DH+ or Ethernet/IP communication links, the network connection to the 1747-KE or 1747-AENTR communication adapter should remain undisturbed during the power supply swap. It is advisable to perform the replacement during a scheduled maintenance window, with the RSLogix 500 program backed up to an offline file and the 1747-UIC USB programming cable connected to a laptop for immediate post-swap verification. After restoring power, confirm that the SLC processor returns to RUN mode and that all I/O module status indicators show normal operation before releasing the line.
In multi-rack configurations using a 1746-A13 chassis with a 1746-C7 or 1746-C9 expansion cable connecting to a remote I/O rack, verify that the remote rack’s own power supply — typically a 1746-P1 or 1746-P2 — is also assessed for age and load margin. A power supply failure in the remote rack can produce symptoms that are easily misdiagnosed as a processor or communication fault, extending troubleshooting time unnecessarily.
Where the retrofit scope includes HMI panel updates, engineers working with PanelView 550 or PanelView 600 terminals connected via DH-485 should confirm that the HMI application file references the correct node address for the SLC processor after any rack reconfiguration. Node address conflicts on the DH-485 network are a common source of post-retrofit communication faults that can delay return-to-service.
Downtime Control During System Migration
Minimizing unplanned downtime during a 1746-P4 swap requires preparation at three levels: program protection, hardware staging, and communication continuity. Before de-energizing the control cabinet, upload the current SLC 500 program from the processor to an offline RSLogix 500 project file and verify the checksum against the last known-good backup. This step protects against data loss in the event the processor’s battery-backed RAM has degraded — a common condition in systems that have been in service for more than five years.
Hardware staging involves pre-configuring the replacement 1746-P4 on a bench if possible, confirming the unit powers up correctly under a dummy load before installation. Once the cabinet is de-energized and the failed supply is removed, inspect the backplane connector on the chassis for bent pins or corrosion before seating the new unit. Re-torque all terminal screws to the specified value and restore AC power incrementally if a variable autotransformer is available.
For processes where even brief interruptions are costly, consider deploying a temporary 1747-L553 or 1747-L563 processor with a pre-loaded program image in a portable rack as a hot-standby arrangement during the transition. While the SLC 500 platform does not natively support redundant power supplies, this approach allows the field I/O to be re-connected to the standby processor within minutes, maintaining control continuity while the primary rack is serviced. Once the 1746-P4 is installed and verified, the field I/O is reconnected to the primary rack and the standby unit is removed.
Post-installation, run a full I/O force test on all critical outputs before returning the system to automatic mode. Document the replacement in the site maintenance log, including the new unit’s serial number, installation date, and the technician’s name, to support future warranty claims and audit requirements.
Retrofit Support FAQ
Q1: Is the 1746-P4 a direct drop-in replacement for the 1746-P2 or 1746-P3?
Yes. The 1746-P4 uses the same physical form factor and backplane connector as the 1746-P2 and 1746-P3. No chassis modification is required. The primary difference is output capacity — the 1746-P4 provides 10A at 5VDC versus 5A (P2) or 8A (P3), making it suitable for fully populated racks with high-density I/O modules.
Q2: What pre-shipment testing is performed on the 1746-P4?
Each unit undergoes functional power-on testing prior to dispatch, including output voltage verification at 5VDC and 24VDC rails, overcurrent protection response, and visual inspection of the backplane connector and terminal block. A test report is available upon request. All units are covered by a 12-month warranty from the date of shipment.
Q3: Can the 1746-P4 support a fully loaded 1746-A13 chassis with mixed analog and digital I/O?
In most configurations, yes. A fully populated 1746-A13 chassis with a mix of 1746-IB16 digital input, 1746-OB16 digital output, and 1746-NI4 analog input modules typically draws between 6A and 8A at 5VDC. The 1746-P4’s 10A rating provides adequate margin. However, always calculate the actual backplane load from the module specifications before finalizing the supply selection.
Q4: What should I verify during commissioning after installing the 1746-P4?
After restoring power, confirm: (1) the SLC processor returns to RUN mode without fault codes; (2) all I/O module status LEDs indicate normal operation; (3) the 24VDC auxiliary output is within tolerance for any field devices powered from the supply; (4) DH+ or DH-485 communication links re-establish without node conflicts; and (5) the HMI display reflects live process data. Log the commissioning results and retain for warranty and maintenance records.