ProSoft 2150-AGA/1747-KE Retrofit-Ready DF1-DH485 Gateway for SLC 500 Control Systems
The ProSoft 2150-AGA/1747-KE is a proven, retrofit-ready communication gateway engineered as a direct functional replacement for the discontinued Allen-Bradley 1747-KE module. Designed to bridge DF1 full-duplex or half-duplex serial communication with the DH-485 network, this module enables seamless integration of legacy SLC 500 control systems with modern SCADA platforms, HMI panels, and programming environments — without requiring a full controller replacement or extensive rewiring.
For facilities operating aging SLC 5/01, SLC 5/02, SLC 5/03, or SLC 5/04 processors, the 2150-AGA/1747-KE provides a cost-effective migration path that preserves existing ladder logic, retains DH-485 network topology, and minimizes planned downtime during the upgrade window. Every unit shipped by SMARTNEXMSK is fully tested under load conditions and backed by a 12-month warranty.
Upgrade Compatibility Table
| Parameter | 1747-KE (Original) | ProSoft 2150-AGA/1747-KE (Replacement) |
|---|---|---|
| Form Factor | SLC 500 single-slot I/O module | SLC 500 single-slot I/O module (drop-in) |
| Backplane Interface | SLC 500 backplane (1746 chassis) | SLC 500 backplane (1746 chassis) — fully compatible |
| Serial Port (DF1) | RS-232 DB-9, DF1 full/half duplex | RS-232 DB-9, DF1 full/half duplex — identical pinout |
| Network Port (DH-485) | RJ-45 / terminal block, DH-485 | RJ-45 / terminal block, DH-485 — same wiring |
| Power Consumption | ~150 mA @ 5 VDC backplane | ~160 mA @ 5 VDC — verify chassis power budget |
| Communication Protocol | DF1 ↔ DH-485 | DF1 ↔ DH-485 — no protocol reconfiguration needed |
| Module Address | Slot-based, configured in RSLogix 500 | Slot-based — re-use existing I/O configuration file |
| RSLogix 500 Compatibility | Full | Full — existing .RSS project files load without modification |
| HMI Compatibility | PanelView, FactoryTalk View SE/ME via DH-485 | Same — no HMI screen or tag remapping required |
| Retrofit Recommendation | Discontinued / EOL | Direct drop-in replacement — recommended upgrade path |
| Commissioning | DIP switch node address + baud rate | DIP switch node address + baud rate — identical procedure |
| Warranty | N/A (EOL) | 12-Month Warranty — tested before shipment |
Retrofit Planning for Existing Automation Systems
A successful retrofit of the 2150-AGA/1747-KE into an operating SLC 500 system begins well before the physical swap. Engineers should start by auditing the existing 1746 chassis — confirming available slot positions, verifying the chassis power supply (typically a 1746-P2 or 1746-P4) can support the replacement module’s 5 VDC draw, and documenting the current DIP switch settings for node address and baud rate on the outgoing 1747-KE.
Terminal wiring on the DH-485 side uses the same RJ-45 or screw-terminal connection as the original module, so existing cable runs to other DH-485 nodes — such as a 1747-AIC link coupler or additional SLC 500 racks — do not need to be disturbed. On the DF1 serial side, the RS-232 DB-9 cable connecting to the SCADA host, a 1784-U2DHP USB-to-DH+ adapter, or a PC running RSLinx Classic can be reused without modification.
Before powering down the rack, back up the full RSLogix 500 project file (.RSS) from the SLC processor — whether a SLC 5/03, SLC 5/04, or SLC 5/05 — using RSLogix 500 or RSLogix Micro. This preserves all rung logic, data file configurations, and the I/O configuration table that maps the gateway’s slot address. Because the 2150-AGA/1747-KE occupies the same slot and presents an identical module profile to the SLC backplane, the existing I/O configuration file requires no edits after the swap.
For systems where the DH-485 network also carries traffic from a 1747-SDN DeviceNet Scanner or communicates upstream through a 1756-DHRIO bridge module in a ControlLogix rack, verify that the node address assigned to the replacement gateway does not conflict with other active nodes on the network. A quick DH-485 node scan using RSLinx Classic will confirm network topology before the cutover.
If the control cabinet also houses a PanelView 550 or PanelView 600 HMI communicating over DH-485, no changes to the HMI application or tag database are required — the replacement gateway maintains the same node address and protocol behavior as the original 1747-KE. Similarly, any 1747-PIC programming cable connections used for local laptop access remain fully functional with the 2150-AGA/1747-KE installed.
Downtime Control During System Migration
Minimizing unplanned downtime is the primary concern for any SLC 500 gateway replacement. The 2150-AGA/1747-KE’s drop-in compatibility means the physical swap — removing the 1747-KE and seating the replacement — takes under five minutes once the chassis is de-energized. The critical time investment lies in pre-swap preparation: backing up the processor program, photographing terminal wiring, recording DIP switch positions, and confirming the chassis power budget.
A recommended cutover sequence is: (1) notify all operators and place the process in a safe hold state; (2) de-energize the 1746 chassis; (3) remove the 1747-KE and install the 2150-AGA/1747-KE in the same slot with identical DIP switch settings; (4) re-energize the chassis and confirm the module’s status LED indicates normal operation; (5) reconnect RSLinx Classic and verify the gateway appears on the DH-485 network at the expected node address; (6) perform a short online program verification in RSLogix 500 to confirm all I/O status bits are healthy; (7) release the process from hold state and resume normal production.
Because no program changes are required and the HMI communication path is preserved, operators typically see zero change in screen behavior or alarm states after the swap. SMARTNEXMSK recommends keeping the removed 1747-KE module on-site as a temporary spare until the replacement has completed at least one full production cycle, providing an additional safety net during the validation period.
All units are shipped with pre-shipment functional testing documentation. In-stock inventory ensures same-week dispatch, reducing the window between fault identification and system restoration — a critical factor for facilities without redundant communication paths.
Retrofit Support FAQ
Q1: Is the ProSoft 2150-AGA/1747-KE a true drop-in replacement for the Allen-Bradley 1747-KE?
Yes. The 2150-AGA/1747-KE occupies a single SLC 500 slot in any 1746 chassis, uses the same DIP switch configuration for node address and baud rate, and presents an identical module profile to the SLC backplane. Existing RSLogix 500 project files, DH-485 wiring, and DF1 serial cables require no modification.
Q2: Will my PanelView HMI or SCADA system require reconfiguration after the swap?
No. Because the 2150-AGA/1747-KE maintains the same DH-485 node address and DF1 protocol behavior as the original 1747-KE, HMI applications (PanelView 550, PanelView 600, FactoryTalk View ME) and SCADA drivers communicating via RSLinx Classic will continue to operate without tag remapping or driver reconfiguration.
Q3: What pre-shipment testing is performed, and what does the 12-month warranty cover?
Every 2150-AGA/1747-KE unit is powered up, subjected to DF1 and DH-485 communication load testing, and verified for correct backplane enumeration before dispatch. The 12-month warranty covers hardware defects and communication failures under normal operating conditions. Units that fail in service are replaced or refunded — contact [email protected] to initiate a warranty claim.
Q4: What if my chassis power supply cannot support the replacement module?
The 2150-AGA/1747-KE draws approximately 160 mA at 5 VDC from the backplane — marginally higher than the original 1747-KE. In most installations the existing 1746-P2 or 1746-P4 power supply has sufficient headroom. If the chassis is already near its power budget limit, consider replacing the power supply with a higher-capacity unit before the gateway swap. Our technical team can assist with power budget calculations prior to your order.